| SPECIFICATIONS |
MEP 95-501A
NSN: 6115-01-435-1567 |
MEP 95-531A
NSN: 6115-01-435-1565 |
| Power Output |
2 kW |
2 kW |
| Voltage |
28 VDC |
120 VAC |
Quality Power |
< 5.0% Ripple |
< 12% Deviation Factor |
| Weight |
140 lbs. with 4 hours of fuel |
152 lbs. with 4 hours of fuel |
| Dimensions |
29.5” x 16.0” x 21.7” |
| Engine |
Single Cylinder Air-cooled Diesel Engine |
| Fuel |
JP-8, DL-2, DF2 |
| Operating Temperature |
-32ºC (-25ºF) To 49ºC (120ºF) |
| Additional Features |
Recoil Manual Start
Electric Start with NATO Slave
EMI Suppressed
Military Technical Manual
Complete Logistic Support |
| TEST |
SPECIFICATIONS |
| Insulation resistance test |
>2000 M ohm |
| High potential test |
1500 VDC, 1 min. |
| Winding resistance test |
<5% variation |
| Start and stop test |
14 sec./4 sec. |
| Circuit interrupter test (short circuit) |
0.34 sec. |
| Circuit interrupter test (overload current) |
<110 sec. @ 125% Load |
| Low oil pressure protective device test |
12-15 psi |
| Instrument Accuracy |
Voltmeter <± 3%
Load meter <± 5% Rated load
Freq Meter (Mode III) <± 1% Rated freq |
| Voltage waveform test (harmonic analysis, Mode III sets only) |
Deviation Factor <16%
Frequency Harmonics <15% |
| Frequency (Speed) and voltage stability test (long-term) |
Mode III <4%
Mode IV <2% |
| Maximum power test |
2.0 kW continuous , 2.1 KW Minimum 2 hrs. |
| Ripple voltage test (Mode IV sets only) |
<7% |
| Noise level test |
<79 dBA |
| Maintainability |
<0.033 |
| Reliability test |
1000 hours min. |
| Endurance test |
1000 hours |
| Starting and operating test (moderate cold electric start) |
-32ºC(-25ºF), 5 min. |
| Starting and operating test (moderate cold manual crank) |
-5ºC(+23ºF), 5 min. |
| High temperature test |
+49ºC(+120ºF) |
| Humidity test |
5 cycles of 48 hrs @ 95% |
| Electromagnetic interference (UM04) |
RE02, CE04, RS03 |
| Extreme Cold Storage |
-54º C (-65º F) |
| Frequency Regulation |
<5.6% |
| Voltage Regulation |
<4% |